High Speed Fuses - North American,FWX 250V: 35-2500A
High Speed Fuses - North American
FWX 250V: 35-2500A
FWX
Specifications
Decription:
North American style stud-mount and flush-end fuses.
Dimensions:
See Dimensions illustrations.
Ratings:
Agency Information:
CE, UL Recognized & CSA Component Acceptance on 35-800A fuses (20kA IR @250Vdc).
Features and Benefits:
@ Excellent dc performance
@ Low arc voltage and low
energy let-through (I2t)
@ Superior cycling capability
@ Low arc voltage and low
energy let-through (I2t)
@ Superior cycling capability
Typical Applications:
@ DC common bus
@ DC drives
@ Power converters/rectifiers
@ Reduced voltage starters
@ DC drives
@ Power converters/rectifiers
@ Reduced voltage starters
Arc Voltage:
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Total Clearing I2t:
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Power Losses:
Watts loss at rated current is
given in the electrical char
acteristics. The curve allows
the calculation of the power
losses at load currents lower
than the rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
given in the electrical char
acteristics. The curve allows
the calculation of the power
losses at load currents lower
than the rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
Data Sheet:
Catalog Number | Clear at 250V - I2t (A2 Sec) | Pre-arc I2t (A2 Sec) | Rated Current RMS-Amps | Watts Loss | Dimensions (in): Fig. | Dimensions (in): A | Dimensions (in): B | Dimensions (in): C | Dimensions (in): D | Dimensions (in): E | Dimensions (in): F | Dimensions (in): G | Dimensions (in): H | Dimensions (in): J | Dimensions (in): Thread Depth | Note |
FWX-35A | 230 | 50 | 35 | 4.2 | 1 | 3.19 | 0.81 | 1.59 | 2.59 | 2.25 | 0.34 | 0.63 | 0.13 | 0.52 | — |
|
FWX-40A | 310 | 60 | 40 | 5.2 | 1 | 3.19 | 0.81 | 1.59 | 2.59 | 2.25 | 0.34 | 0.63 | 0.13 | 0.52 | — |
|
FWX-45A | 390 | 80 | 45 | 5.7 | 1 | 3.19 | 0.81 | 1.59 | 2.59 | 2.25 | 0.34 | 0.63 | 0.13 | 0.52 | — |
|
FWX-50A | 520 | 100 | 50 | 6.0 | 1 | 3.19 | 0.81 | 1.59 | 2.59 | 2.25 | 0.34 | 0.63 | 0.13 | 0.52 | — |
|
FWX-60A | 740 | 140 | 60 | 8.1 | 1 | 3.19 | 0.81 | 1.59 | 2.59 | 2.25 | 0.34 | 0.63 | 0.13 | 0.52 | — |
|
FWX-70A | 1400 | 330 | 70 | 7.2 | 1 | 3.13 | 1.22 | 1.59 | 2.44 | 2.19 | 0.34 | 1.00 | 0.19 | 0.47 | — |
|
FWX-80A | 1850 | 430 | 80 | 8.1 | 1 | 3.13 | 1.22 | 1.59 | 2.44 | 2.19 | 0.34 | 1.00 | 0.19 | 0.47 | — |
|
FWX-90A | 2450 | 570 | 90 | 9.0 | 1 | 3.13 | 1.22 | 1.59 | 2.44 | 2.19 | 0.34 | 1.00 | 0.19 | 0.47 | — |
|
FWX-100A | 3150 | 740 | 100 | 10.0 | 1 | 3.13 | 1.22 | 1.59 | 2.44 | 2.19 | 0.34 | 1.00 | 0.19 | 0.47 | — |
|
FWX-125A | 4850 | 1130 | 125 | 12.5 | 1 | 3.13 | 1.22 | 1.59 | 2.44 | 2.19 | 0.34 | 1.00 | 0.13 | 0.47 | — |
|
FWX-150A | 6950 | 1620 | 150 | 15.7 | 1 | 3.13 | 1.22 | 1.59 | 2.44 | 2.19 | 0.34 | 1.00 | 0.19 | 0.47 | — |
|
FWX-175A | 9300 | 2170 | 175 | 18.5 | 1 | 3.13 | 1.22 | 1.59 | 2.44 | 2.19 | 0.34 | 1.00 | 0.19 | 0.47 | — |
|
FWX-200A | 12000 | 2790 | 200 | 22 | 1 | 3.13 | 1.22 | 1.59 | 2.44 | 2.19 | 0.34 | 1.00 | 0.19 | 0.47 | — |
|
FWX-225A | 14700 | 3210 | 225 | 24 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-250A | 18100 | 3960 | 250 | 27 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-275A | 21600 | 4720 | 275 | 31 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-300A | 27300 | 6000 | 300 | 32 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-350A | 48600 | 10600 | 350 | 39 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-400A | 66100 | 14500 | 400 | 44 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-450A | 101000 | 22100 | 450 | 49 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-500A | 128000 | 28000 | 500 | 54 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-600A | 188000 | 41100 | 600 | 62 | 1 | 3.84 | 1.50 | 1.59 | 2.94 | 2.25 | 0.41 | 1.00 | 0.25 | 0.75 | — |
|
FWX-700A | 190000 | 48800 | 700 | 72 | 1 | 3.84 | 2.00 | 1.59 | 3.03 | 2.28 | 0.41 | 1.50 | 0.25 | 0.78 | — |
|
FWX-800A | 230000 | 59000 | 800 | 84 | 1 | 3.84 | 2.00 | 1.59 | 3.03 | 2.28 | 0.41 | 1.50 | 0.25 | 0.78 | — |
|
FWX-1000AH | 360000 | 44000 | 1000 | 100 | 2 | 2.59 | 3.00 | 1.50 | — | — | — | — | — | — | 3/8"-24 x 1/2" |
|
FWX-1200AH | 750000 | 92000 | 1200 | 103 | 2 | 2.59 | 3.00 | 1.50 | — | — | — | — | — | 3/8"-24 x 1/2" |
| |
FWX-1500AH | 880000 | 120000 | 1500 | 140 | 3 | 2.59 | 3.50 | 1.50 | 1.50 | — | — | — | — | — | 3/8"--24 x 1/2" |
|
FWX-1600AH | 1200000 | 160000 | 1600 | 140 | 3 | 2.59 | 3.50 | 1.50 | 1.50 | — | — | — | — | — | 3/8"--24 x 1/2" |
|
FWX-2000AH | 2300000 | 320000 | 2000 | 151 | 3 | 2.59 | 3.50 | 1.50 | 1.50 | — | — | — | — | — | 3/8"--24 x 1/2" |
|
FWX-2500AH | 4700000 | 670000 | 2500 | 163 | 3 | 2.59 | 3.50 | 1.50 | 1.50 | — | — | — | — | — | 3/8"--24 x 1/2" |
|