High Speed Fuses - North American,FWA 130V: 1000-4000A

High Speed Fuses - North American
FWA 130V: 1000-4000A


FWA - 130V
Specifications
Decription:
North American style flush-end high speed fuses.
Dimensions:
See Dimensions illustrations.
Ratings:
Volts:- 130Vac
Amps:- 1000-4000A
IR:- 200kA RMS Sym.
 - 50kA @130Vdc
Agency Information:
CE, UL Recognized on 1000-2000A fuses
Features and Benefits:
@ Excellent dc performance
@ Low arc voltage and low energy let-through (I2t)
@ Low watts loss
@ Superior cycling capability
Typical Applications:
@ DC common bus
@ DC drives
@ Power converters/rectifiers
@ Reduced voltage starters
Arc Voltage:
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Total Clearing I2t:
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Power Losses:
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Data Sheet:
Catalog Number Pre-arc I2t (A2 Sec) Rated Current RMS-Amps Clear at 130V - I2t (A2 Sec) Watts Loss Dimensions (in): Fig. Dimensions (in): B Dimensions (in): C Dimensions (in): D Dimensions (in): Thread Depth Note
FWA-1000AH 170000 1000 460000 60 1 2.0 1.0 Tapped 3/8"-24 x 1/2"
  • Watts loss provided at
    rated current.
FWA-1200AH 270000 1200 730000 70 1 3.0 1.0 Tapped 3/8"-24 x 1/2"
  • Watts loss provided at
    rated current.
FWA-1500AH 520000 1500 1400000 78 1 2.0 1.0 Tapped 3/8"-24 x 1/2"
  • Watts loss provided at
    rated current.
FWA-2000AH 860000 2000 2400000 108 1 2.0 1.0 Tapped 3/8"-24 x 1/2"
  • Watts loss provided at
    rated current.
FWA-2500AH 1500000 2500 4100000 130 1 3.0 1.5 Tapped 1/2"-20 x 1/2"
  • Watts loss provided at
    rated current.
FWA-3000AH 2100000 3000 5700000 150 1 3.0 1.5 Tapped 1/2"-20 x 1/2"
  • Watts loss provided at
    rated current.
FWA-4000AH 9200000 4000   257 2 3.5 1.5 1.5 Tapped 1/2"-20 x 1/2"
  • Watts loss provided at
    rated current.